Household Wiring FAQ

Part 2 of 2

From: clewis@ferret.ocunix.on.ca (Chris Lewis)

Last-modified: Mon Nov 14 01:03:29 EST 1994

			Copyright 1991, 1992, 1993
		      Chris Lewis and Steven Bellovin

		Redistribution for profit, or in altered content/format
		prohibited without permission of the authors.
		Redistribution via printed book or CDROM expressly
		prohibited without consent of the author.  Any other
		redistribution must include this copyright notice and
		attribution.

The latest FAQ can always be obtained from:

    ftp://rtfm.mit.edu/pub/usenet/news.answers/electrical-wiring/part[1-2]

------------------------------
Subject: What kind of outlets do I need in a kitchen?

	The NEC requires at least two 20 amp ``small appliance
	circuits'' for kitchen counters.  The CEC requires split-duplex
	receptacles.  Outlets must be installed such that no point is more
	than 24" (NEC) (900 mm CEC) from an outlet.  Every counter wider
	than 12" (NEC) or 300 mm (CEC) must have at least one outlet.
	The circuit these outlets are on may not feed any outlets except
	in the kitchen, pantry, or dining room.  Furthermore, these circuits
	are in addition to any required for refrigerators, stoves, microwaves,
	lighting, etc.  Non-dedicated outlets within 6' of a sink *must* be
	protected by a GFCI (NEC only).

	Split duplex receptacles are fed with a 220V circuit.  The tab
	is broken on the hot side of the outlet, and one hot goes to
	the upper outlet, and the other hot goes to the lower outlet.
	The neutral connects to both outlets through one screw.  When
	"carrying through" to another outlet, the neutral must be
	pigtailed, such that removing the outlet, or having the neutral
	connection fall off or burn out doesn't cause the neutral to
	disconnect from downstream outlets ("loose neutral" problems -
	see "What does it mean when the lights brighten...").

------------------------------
Subject: Where must outlets and switches be in bathrooms?

	There must be at least one outlet in each bathroom, adjacent to
	the sink, in addition to any outlet that may be incorporated in
	the light fixture.  All such outlets *must* be GFCI-protected.

	The NEC says that switches may not be installed inside bathtubs
	or showers.  The CEC says that switches may not be installed
	"within reach" of bathtubs or showers (consult an inspector
	if you can't make it at least four feet).

------------------------------
Subject: General outlet placement rules/line capacities

	We paraphrase CEC 26-702 (NEC: 210-52 through 210-63)

	Note: In laying out receptacle outlets, consideration shall be
	given to the placement of electrical baseboards, hot air
	registers, hot water or steam registers, with a view of
	eliminating cords having to pass over hot or conductive
	surfaces wherever possible.

	NEC:  You're not allowed to put outlets over electric
	baseboards.  That, coupled with the spacing requirements, more
	or less mandates the use of baseboards with integral outlets.
	Note that such outlets are fed by a different branch circuit
	than the heating elements.

	2. Except as otherwise required, receptacles shall be installed
	in the finished walls of every room or area, other than
	kitchens, bathrooms, hallways, laundry rooms, utility rooms or
	closets, so that no point along the floor line of any usable
	wall space is more than 1.8m (6') horizontally from a
	receptacle in that or an adjoining space, such distance being
	measured along the floor line of the wall spaces involved.

	Fixed dividers, counters, etc., are considered wall space.
	Floor outlets do not satisfy the requirement unless they are
	``near'' the wall.  Insofar as practical, outlets should be
	spaced equidistantly.

	3. At least one duplex receptacle shall be provided in each
	enclosed area such as a balcony or porch that is not classified
	as a finished room or area.

	[NEC doesn't seem to have this rule.]

	4. The receptacles referred to in (2) and (3) shall be duplex
	receptacles or equivalent number of single receptacles.

	5. "Usable wall space" is defined as any wall space 900mm (3',
	NEC 2') or more in width, not to include doorways, areas
	occupied by a door when fully opened, windows which extend to
	the floor, fireplaces or other permanent installations that
	would limit the use of the wall space.

	6.  See kitchen counter requirements.  At least one duplex
	receptacle in eat-in dining area.

	[We don't think the latter part is in the NEC.  Also, the NEC
	says that the two 20-amp small appliance circuits can't go
	outside of the kitchen, dining room, pantry, etc., nor can they
	be used for anything else, except for things like clock
	outlets, stove accessory outlets, etc.]

	7. Receptacles shall not be mounted facing up in the work
	surfaces or counters of the kitchen or dining area.

	8. No point in a hallway within a dwelling unit shall be more
	than 4.5m (15', NEC 10') from a duplex receptacle as measured
	by the shortest path which the supply cord of an appliance
	connected to the receptacle would follow without passing
	through an openning fitted with a door.  (vacuum-cleaner
	rule).

	9. At least one duplex receptacle shall be provided: in laundry
	room, utility room and any unfinshed basement area

	[NEC: see GFCI requirements.  There must be a dedicated 20 amp
	laundry receptacle, with no other outlets, plus an additional
	unfinished basement receptacle.  Any attic or crawl space with
	heating or air conditioning equipment must have a receptacle.
	(this is probably in the CEC too.)]

	10, 11, 12, 13:  See bathroom requirements, GFCI, washing
	machine outlet placement.

	14, 15. Outlets shall not be placed in ironing cabinets,
	cupboards, wall cabinets, nor in similar enclosures except
	where they're for specific non-heating appliances (including
	microwave) in the enclosure.

	[NEC: No such requirement.  Are you sure Steven?]

	16, 17. For each single-family dwelling, at least one duplex
	receptacle shall be installed outdoors to be readily available
	from ground level (see GFCI requirements).  Appendix B
	(additional notes) suggests front and back outlets to be
	controlled by an interior switch.

	[NEC:  One in front, one in back.  No discussion of them being
	switched.]

	18. At least one duplex receptacle shall be provided for each
	car space in a garage or carport.

	[NEC:  For an attached garage, or detached garage with electric
	service -- but there is no requirement that detached garages
	have power.  This remark is probably relevant to CEC as well.]

	19. For the purposes of this rule, all receptacles shall be of
	the grounding type, configuration 5-15R (standard 110V/15A 3
	prong).

	20. Any receptacle that is part of a lighting fixture or
	appliance that is > 1.7m (5 feet) above the floor, or in
	cabinets or cupboards, is not counted in the above rules.

	21. Where a switched duplex outlet is used in lieu of a light
	outlet and fixture, the receptacle shall be considered one of
	the wall mounted receptacles required here.

	22. At least one duplex receptacle shall be provided for a
	central vacuum system if the ducting is installed.

	[NEC:  couldn't find an equivalent rule.]

	Capacities: Knight recommends no more than 10 outlets per
	circuit.  Some US references talk about a limit of 12.  There
	appears to be a wattage/area/outlet count calculation somewhere
	in the NEC.  20A circuits may have different rules.

	It is open to considerable debate whether you should mix
	general lighting and outlets on individual circuits.  Knight
	recommends it.  Some netters don't.  I tend towards the former
	for load balancing reasons.

	NEC: There's a new rule on outdoor outlets.  If exposed to the
	weather, and if used for unattended equipment (pool filters,
	outdoor lighting, etc.), the outlet must still be weatherproof
	even when the device is plugged in.

------------------------------
Subject: What is Romex/NM/NMD?  What is BX?  When should I use each?

	Romex is a brand name for a type of plastic insulated wire.
	Sometimes called non-metallic sheath.  The formal name is NM.
	This is suitable for use in dry, protected areas (ie: inside
	stud walls, on the sides of joists etc.), that are not subject
	to mechanical damage or excessive heat.  Most newer homes are
	wired almost exclusively with NM wire.  There are several
	different categories of NM cable.

	BX cable -- technically known as armored cable or "AC" has a
	flexible aluminum or steel sheath over the conductors and is
	fairly resistant to damage.

	TECK cable is AC with an additional external thermoplastic
	sheath.
	
	Protection for cable in concealed locations: where NM or AC cable
	is run through studs, joists or similar wooden members, the outer
	surface of the cable must be kept at least 32mm/1.25" (CEC & NEC)
	from the edges of the wooden members, or the cable should be protected
	from mechanical injury.  This latter protection can take the form of
	metal plates (such as spare outlet box ends) or conduit.

	[Note: inspector-permitted practice in Canada suggests that armored
	cable, or flexible conduit can be used as the mechanical protection,
	but this is technically illegal.]

	Additional protection recommendations: [These are rules in the
	Canadian codes.  The 1993 NEC has many changes that bring
	it close to these rules.  These are reasonable answers to the
	vague "exposed to mechanical damage" in both the NEC and CEC.]

	    - NM cable should be protected against mechanical damage
	      where it passes through floors or on the surface of walls
	      in exposed locations under 5 feet from the floor.
	      Ie: use AC instead, flexible conduit, wooden guards etc.
	    - Where cable is suspended, as in, connections to furnaces
	      or water heaters, the wire should be protected.  Canadian
	      practice is usually to install a junction or outlet
	      box on the wall, and use a short length of AC cable
	      or NM cable in flexible conduit to "jump" to the appliance.
	      Stapling NM to a piece of lumber is also sometimes used.
	    - Where NM cable is run in close proximity to heating
	      ducts or pipe, heat transfer should be minimized by
	      means of a 25mm/1" air space, or suitable insulation
	      material (a wad of fiberglass).
	    - NM cable shall be supported within 300mm/1' of every box
	      or fitting, and at intervals of no more than 1.5m/5'.
	      Holes in joists or studs are considered "supports".
	      Some slack in the cable should be provided adjacent to
	      each box.  [while fishing cable is technically in violation,
	      it is permitted where "proper" support is impractical]
	    - 2 conductor NM cable should never be stapled on edge.
	      [Knight also insists on only one cable per staple, referring
	      to the "workmanship" clause, but this seems more honoured
	      in the breach...]
	    - cable should never be buried in plaster, cement or
	      similar finish, except were required by code [Ie: cable
	      burial with shallow bedrock.].
	    - cable should be protected where it runs behind baseboards.
	    - Cable may not be run on the upper edge of ceiling joists
	      or the lower edges of rafters where the headroom is more
	      than 1m (39").

	Whenever BX cable is terminated at a box with a clamp, small
	plastic bushings must be inserted in the end of the cable to
	prevent the clamps forcing the sharp ends of the armor through
	the insulation.

	Whenever BX cable is buried in thermal insulation, 90C
	wire should be selected, but derated in current carrying
	capacity to 60C.

	BX is sometimes a good idea in a work shop unless covered by
	solid wall coverings.

	In places where damage is more likely (like on the back wall of
	a garage ;-), you may be required to use conduit, a
	UL- (or CSA-) approved metal pipe.  You use various types of
	fittings to join the pipe or provide entrance/exit for the
	wire.

	Service entrances frequently use a plastic conduit.

	In damp places (eg: buried wiring to outdoor lighting) you will
	need special wire (eg: CEC NMW90, NEC UF).  NMW90 looks like
	very heavy-duty NMD90.  You will usually need short lengths of
	conduit where the wire enters/exits the ground.  [See underground
	wiring section.]

 	Thermoplastic sheath wire (such as NM, NMW etc.) should not be
 	exposed to direct sunlight unless explicitly approved for that
 	purpose.

	Many electrical codes do not permit the routing of wire through
	furnace ducts, including cold air return plenums constructed
	by metal sheeting enclosing joist spaces.   The reason for this
	is that if there's a fire, the ducting will spread toxic gasses
	from burning insulation very rapidly through the building.
	Teflon insulated wire is permitted in plenums in many areas.
	
 	Canada appears to use similar wire designations to the US,
 	except that Canadian wire designations usually include the
 	temperature rating in Celsius.  Eg: "AC90" versus "AC".
	In the US, NM-B is 90 degrees celcius.

	NOTE: local codes vary.  This is one of the items that changes
	most often.  Eg: Chicago codes require conduit *everywhere*.
	There are very different requirements for mobile homes.
	Check your local codes, *especially* if you're doing anything
	that's the slightest out of the ordinary.

	Wire selection table (incomplete - the real tables are enormous,
	uncommon wire types or applications omitted)

	Condition			Type	CEC	NEC

	Exposed/Concealed dry		plastic	NMD90	NM
					armor	AC90	AC
						TECK90

	Exposed/Concealed damp		plastic	NMD90	NMC
					armor	ACWU90
						TECK90

	Exposed/Concealed wet		plastic	NMWU90
					armor	ACWU90
						TECK90
	
	Exposed to weather		plastic	NMWU
						TW etc.
					armor	TECK90
	
	Direct earth burial/		plastic	NMWU*	UF
	Service entrance			RWU
						TWU
					armor	RA90
						TECK90
						ACWU90
	[* NMWU not for service entrance]

------------------------------
Subject: Should I use plastic or metal boxes?

	The NEC permits use of plastic boxes with non-metallic cable
	only.  The reasoning is simple -- with armored cable, the box
	itself provides ground conductor continuity.  U.S. plastic
	boxes don't use metal cable clamps.

	The CEC is slightly different.  The CEC never permits cable
	armor as a grounding conductor.  However, you must still
	provide ground continuity for metallic sheath.  The CEC also
	requires grounding of any metal cable clamps on plastic boxes.

	The advantage of plastic boxes is comparatively minor even for
	non-metallic sheathed cable -- you can avoid making one ground
	connection and they sometimes cost a little less.  On the other
	hand, plastic boxes are more vulnerable to impacts.  For
	exposed or shop wiring, metal boxes are probably better.

	Metal receptacle covers must be grounded, even on plastic
	boxes.  This may be achieved by use of a switch with ground
	connection.

------------------------------
Subject: Junction box positioning?

	A junction box is a box used only for connecting wires together.

	Junction boxes must be located in such a way that they're accessible
	later.  Ie: not buried under plaster.  Excessive use of junction
	boxes is often a sign of sloppy installation, and inspectors may
	get nasty.

------------------------------
Subject: Can I install a replacement light fixture?

	In general, one can replace fixtures freely, subject to a few
	caveats.  First, of course, one should check the amperage
	rating of the circuit.  If your heart is set on installing half
	a dozen 500 watt floodlights, you may need to run a new wire
	back to the panel box.  But there are some more subtle
	constraints as well.  For example, older house wiring doesn't
	have high-temperature insulation.  The excess heat generated by
	a ceiling-mounted lamp can and will cause the insulation to
	deteriorate and crack, with obvious bad results.  Some newer
	fixtures are specifically marked for high temperature wire
	only.  (You may find, in fact, that your ceiling wiring already
	has this problem, in which case replacing any devices is a real
	adventure.)

	Other concerns include providing a suitable ground for some
	fluorescent fixtures, and making sure that the ceiling box and
	its mounting are strong enough to support the weight of a heavy
	chandelier or ceiling fan.  You may need to install a new box
	specifically listed for this purpose.  A 2x4 across the ceiling
	joists makes a good support.  Metal brackets are also available
	that can be fished into ceilings thru the junction box hole and
	mounted between the joists.

	There are special rules for recessed light fixtures such as
	"pot" lamps or heat lamps.  When these are installed in
	insulated ceilings, they can present a very substantial fire
	hazard.  The CEC provides for the installation of pot lamps in
	insulated ceilings, provided that the fixture is boxed in a
	"coffin" (usually 8'x16"x12" - made by making a pair of joists
	12" high, and covering with plywood) that doesn't have any
	insulation.  (Yes, that's 8 *feet* long)

	NEC rules are somewhat less stringent.  They require at least
	3" clearance between the fixture and any sort of thermal
	insulation.  The rules also say that one should not obstruct
	free air movement, which means that a CEC-style ``coffin''
	might be worthwhile.  Presumably, that's up to the local
	inspector.  [The CEC doesn't actually mandate the coffin
	per-se, this seems to be an inspector requirement to make
	absolutely certain that the fixture can't get accidentally
	buried in insulation.  Ie: if you have insulation blown in
	later.]

	There are now fixtures that contain integral thermal cutouts
	and fairly large cases that can be buried directly in
	insulation.  They are usually limited to 75 watt bulbs, and are
	unfortunately, somewhat more expensive than the older types.
	Before you use them, you should ensure that they have explicit
	UL or CSA approval for such uses.  Follow the installation
	instructions carefully; the prescribed location for the sensor
	can vary.

	There does not yet appear to be a heat lamp fixture that is
	approved for use in insulation.  The "coffin" appears the only
	legal approach.

------------------------------
Subject: Noisy fluorescent fixtures, what do I do?

	Many fluorescent fixtures tend to buzz, objectionably so when used in
	residential (rather than warehouse or industrial) situations.  This
	tends to be the result of magnetic/physical resonances at the
	(low) frequencies that standard fixture ballasts operate.  You
	can eliminate this problem by switching to electronic ballasts,
	which operate at a higher (inaudible) frequency.  Unfortunately,
	these are quite expensive.

-----------------------------
Subject: Noisy lights with dimmer switches, what do I do?

	Often, after installing a dimmer switch, or replacing bulbs controlled
	by a dimmer, you'll start hearing objectionable buzzing or humming
	from the bulb.  Sometimes it even interferes with televisions or radios.

	A little theory first.  The voltage on the wiring in your house looks
	like this - a sine wave (forgive the lousy ASCII graphics ;-):

                  ...             ...              ~ +160V
                 .   .           .   .
                .     .         .     .
              ------------------------------------ 0V
                        .     .         .     .
                         .   .           .   .
                          ...             ...      ~ -160V
	
	Most dimmers work by having a solid-state switch called a triac
	in series with the light bulb.  Whenever the voltage passes through
	zero (it does this 120 times per second), the triac turns itself off.
	The control circuitry in the dimmer provides an adjustable delay
	before the triac turns back on.  So, the resulting wave form looks
	like this:

                  ...             ...              ~ +160V
                  |  .            |  .
                  |   .           |   .
              ------------------------------------ 0V
                          |   .           |   .
                          |  .            |  .
                          ...             ...      ~ -160V
	

	As you can see, by varying the turn-on point, the amount of
	power getting to the bulb is adjustable, and hence the light
	output can be controlled.  Voila, a dimmer!

	This is where it gets interesting.  Note the sharp corners.
	According to the Nyquist theorem, those corners effectively
	consist of 60Hz plus varying amounts of other frequencies that
	are multiples of 60Hz.  In some cases up to 1Mhz and more.  The
	wiring in your house acts as an antenna and essentially
	broadcasts it into the air.  Hence TVs and radios can be
	effected.  This is called EMI (Electromagnetic Interference).

	As far as the bulbs are concerned, a bulb consists of a series
	of supports and, essentially, fine coils of wire.   When you
	run current through a coil, it becomes a magnet right?  If
	there's any other metal nearby, it'll move.  Just like a
	solenoid.  Further, when the amount of current flow abruptly
	changes the magnetism change can be much stronger than it is on
	a simple sine wave.  Hence, the filaments of the bulb will tend
	to vibrate more with a dimmer chopping up the wave form, and
	when the filaments vibrate against their support posts, you
	will get a buzz.

	Worse, some dimmers only do half-wave switching, such that the
	one half of the chopped wave form will be absent.  Which means
	that the current flow during the present half will have to be
	much stronger to produce the same amount of light - more EMI
	and more tendency to buzz.

	Solving buzzing problems:  If you have buzzing, it's always
	worth trying to replace the bulb with a different brand.  Some
	cheap bulb brands have inadequate filament support, and simply
	changing to a different brand may help.  Try "rough service" or
	"farm service" bulbs.  They're usually much stronger and better
	supported.

	Chance are, however, that switching bulbs won't make that much
	of a difference.  Perhaps the buzzing will go away at some
	dimmer settings, but not at all.

	Buzzing bulbs are usually a sign of a "cheap" dimmer.  Dimmers
	are supposed to have filters in them.  The filter's job is to
	"round off" the sharp corners in the chopped waveform, thereby
	reducing EMI, and the abrupt current jumps that can cause
	buzzing.  In cheap dimmers, they've economized on the
	manufacturing costs by cost-reducing the filtering, making it
	less effective.  Perhaps the dimmer will be okay at some
	settings, but not others.  Or be very picky about what bulbs to
	use.

	It is our belief that most buzzing problems can be traced down
	to cheap (<$15 dimmers), and most effectively solved by going
	to mid-range ($25-$35) dimmers from respected companies, such
	as Leviton.  One of the authors of this FAQ, after learning
	this lesson, will still use $.89 outlets, but insists on better
	dimmers.  By all means, try a different bulb first.  You may
	get lucky.  If not, it's time to swap dimmers.

	If you have EMI problems, it's almost certain to be a cheap
	dimmer.

-----------------------------
Subject: What does it mean when the lights brighten when a motor starts?

	This usually means that the neutral wire in the panel is
	loose.  Depending on the load balance, one hot wire may end up
	being more than 110V, and the other less than 110V, with
	respect to ground.  This is a very hazardous situation - it can
	destroy your electronic equipment, possibly start fires, and in
	some situations electrocute you (ie: some US jurisdictions
	require the stove frame connected to neutral).

	If this happens, contact your electrical authority immediately
	and have them come and check out the problem.  If you say "loose
	neutral", they will come.

	Note: a brief (< 1 second) brightening is sometimes normal with
	lighting and motors on the same 220V with neutral circuit.  A
	loose main panel neutral will usually show increased brightness
	far longer than one second.  In case of doubt, get help.

------------------------------
Subject: What is 3 phase power?  Should I use it?  Can I get it in my house?

	Three phase power has three "hot" wires, 120 degrees out of
	phase with each other.  These are usually used for large motors
	because it is more "efficient", provides a bit more starting torque,
	and because the motors are simpler and hence cheaper.

	You're most likely to encounter a 3 phase circuit that shows
	110 volts between any hot and ground, and 208 volts between
	any two hots.  The latter shows the difference between a normal
	220V/110V common neutral circuit, which is 240 volts between the
	two hots.  There are 3 phase circuits with different voltages.

	Bringing in a 3 phase feed to your house is usually
	ridiculously expensive, or impossible.  If the equipment you
	want to run has a standard motor mount, it is *MUCH* cheaper to
	buy a new 110V or 220V motor for it.  In some cases it is
	possible to run 3 phase equipment on ordinary power if you have
	a "capacitor start" unit, or use a larger motor as a
	(auto-)generator.  These are tricky, but are a good solution if
	the motor is non-standard size, or too expensive or too big to
	replace.  The Taunton Press book ``The Small Shop'' has an
	article on how to do this if you must.

	Note that you lose any possible electrical efficiency by using
	such a converter.  The laws of thermodynamics guarantee that.

------------------------------
Subject: Is it better to run motors at 110 or 220?

	Theoretically, it doesn't make any difference.  However, there
	is a difference is the amount of power lost in the supply
	wiring.  All things being equal, a 110V motor will lose 4 times
	more power in the house wiring than a 220V motor.  This also
	means that the startup surge loss will be less, and the motor
	will get to speed quicker with 220V.  And in some circumstances,
	the smaller power loss will lead to longer motor life.

	This is usually irrelevant unless the supply wires are more
	than 50 feet long.

------------------------------
Subject: What is this nonsense about 3HP on 110V 15A circuits?

	It is a universal physical law that 1 HP is equal to 746
	watts.  Given heating loss, power factor and other inefficiencies,
	it is usually best to consider 1 HP is going to need 1000-1200
	watts.  A 110V 15A circuit can only deliver 1850 watts to a motor,
	so it cannot possibly be more than approximately 2 HP.  Given rational
	efficiency factors, 1.5HP is more like it.

	Some equipment manufacturers (Sears in particular, most router
	manufacturers in general ;-) advertise a HP rating that is far
	in excess of what is possible.  They are giving you a "stall
	horsepower" or similar.  That means the power is measured when
	the motor is just about to stop turning because of the load.
	What they don't mention is that if you kept it in that
	condition for more than a few seconds your motor will melt - the
	motor is drawing far more current than its continuous rating.

	When comparing motors, compare the continuous horsepower.  This
	should be on the motor nameplate.  If you can't find that figure,
	check the amperage rating, which is always present.

------------------------------
Subject: How should I wire my shop?

	As with any other kind of wiring, you need enough power for all
	devices that will be on simultaneously.  The code specifies
	that you should stay under 80% of the nominal capacity of the
	circuit.  For typical home shop use, this means one circuit for
	the major power tools, and possibly one for a dust collector or
	shop vac.  Use at least 12 gauge wire -- many power tools have
	big motors, with a big start-up surge.  If you can, use 20 amp
	breakers (NEC), though CEC requires standard 20A receptacles
	which means you'd have to "replug" all your equipment.  Lights
	should either be on a circuit of their own -- and not shared
	with circuits in the rest of the house -- or be on at least two
	separate circuits.  The idea is that you want to avoid a
	situation where a blade is still spinning at several thousand
	RPM, while you're groping in the dark for the OFF switch.

	Do install lots of outlets.  It's easier to install them in the
	beginning, when you don't have to cut into an existing cable.
	It's useful if at least two circuits are accessible at each
	point, so you can run a shop vac or a compressor at the same
	time as the tool you really want.  But use metal boxes and
	plates, and maybe even metal-sheathed cable; you may have
	objects flying around at high speeds if something goes a bit
	wrong.

	Note that some jurisdictions have a "no horizontal wiring"
	rule in workshops or other unfinished areas that are used
	for working.  What this means is that all wiring must be
	run along structural members.  Ie: stapled to studs.

	Other possible shop circuits include heater circuits, 220V
	circuits for some large tools, and air compressor circuits.
	Don't overload circuits, and don't use extension cords if you
	can help it, unless they're rated for high currents.  (A coiled
	extension cord is not as safe as a straight length of wire of
	the same gauge.  Also, the insulation won't withstand as much
	heat, and heat dissipation is the critical issue.)

	If your shop is located at some remove from your main panel,
	you should probably install a subpanel, and derive your shop
	wiring from it.  If you have young children, you may want to
	equip this panel with a cut-off switch, and possibly a lock.
	If you want to install individual switches to ``safe''
	particular circuits, make sure you get ones rated high enough.
	For example, ordinary light switches are not safely able to
	handle the start-up surge generated by a table saw.  Buy
	``horsepower-rated'' switches instead.

	Finally, note that most home shops are in garages or unfinished
	basements; hence the NEC requirements for GFCIs apply.  And
	even if you ``know'' that you'd never use one of your shop
	outlets to run a lawn mower, the next owner of your house might
	have a different idea.

	Note: Fine Woodworking magazine often carries articles on shop
	wiring.  April 1992 is one place to start.

------------------------------
Subject: Doorbell/telephone/cable other service wiring hints.

	Auxiliary services, such as cable, telephone, doorbell, furnace
	control circuits etc. are generally considered to be "class 2"
	wiring by both the CEC and NEC.

	What this generally means is:

		1) class 2 and house power should not share conduit or
		   termination boxes.
		2) class 2 and house power should be 12" apart in walls
		   except where necessary.
		3) cross-over should be at 90 degrees.
	
	While the above may not be strictly necessary to the code, it
	is advantageous anyways - paralleling house power beside telephone
	lines tends to induce hum into the telephone.  Or could interfere
	with fancier furnace control systems.

	With telephone wiring, twisted pair can alleviate these problems,
	and there are new cable types that combine multiple services into
	one sheath.  Consult your inspector if you really want to violate
	the above recommendations.

------------------------------
Subject: Underground Wiring

	You will need to prepare a trench to specifications, use
	special wire, protect the wire with conduit or special plastic
	tubing and possibly lumber (don't use creosoted lumber, it rots
	thermoplastic insulation and acts as a catalyst in the corrosion
	of lead).  The transition from in-house to underground wire is
	generally via conduit.  All outdoor boxes must be specifically
	listed for the purpose, and contain the appropriate gaskets,
	fittings, etc.  If the location of the box is subject to immersion
	in water, a more serious style of water-proof box is needed.  And
	of course, don't forget the GFCIs.

	The required depths and other details vary from jurisdiction to
	jurisdiction, so we suggest you consult your inspector about
	your specific situation.

	A hint: buy a roll of bright yellow tape that says "buried power
	line" and bury it a few inches above where the wire has been placed.

------------------------------
Subject: Aluminum wiring

	During the 1970's, aluminum (instead of copper) wiring became
	quite popular and was extensively used.  Since that time,
	aluminum wiring has been implicated in a number of house fires,
	and most jurisdictions no longer permit it in new installations.
	We recommend, even if you're allowed to, that do not use it for new
	wiring.

	But don't panic if your house has aluminum wiring.  Aluminum
	wiring, when properly installed, can be just as safe as copper.
	Aluminum wiring is, however, very unforgiving of improper
	installation.  We will cover a bit of the theory behind potential
	problems, and what you can do to make your wiring safe.

	The main problem with aluminum wiring is a phenomenon known as
	"cold creep".  When aluminum wiring warms up, it expands.  When
	it cools down, it contracts.  Unlike copper, when aluminum goes
	through a number of warm/cool cycles it loses a bit of tightness each
	time.  To make the problem worse, aluminum oxidises, or corrodes
	when in contact with certain types of metal, so the resistance
	of the connection goes up.  Which causes it to heat up and corrode/
	oxidize still more.  Eventually the wire may start getting very hot,
	melt the insulation or fixture it's attached to, and possibly even
	cause a fire.

	Since people usually encounter aluminum wiring when they move
	into a house built during the 70's, we will cover basic points
	of safe aluminum wiring.  We suggest that, if you're
	considering purchasing a home with aluminum wiring, or have
	discovered it later, that you hire a licensed electrician or
	inspector to check over the wiring for the following things:

	    1) Fixtures (eg: outlets and switches) directly attached to
	       aluminum wiring should be rated for it.  The device will
	       be stamped with "Al/Cu" or "CO/ALR".  The latter supersedes
	       the former, but both are safe.   These fixtures are somewhat
	       more expensive than the ordinary ones.

	    2) Wires should be properly connected (at least 3/4 way around
	       the screw in a clockwise direction).  Connections should be
	       tight.  While repeated tightening of the screws can make the
	       problem worse, during the inspection it would pay off to snug
	       up each connection.

	       Note that aluminum wiring is still often used for the
	       main service entrance cable.  It should be inspected.

	    3) "push-in" terminals are an extreme hazard with aluminum wire.
	       Any connections using push-in terminals should be redone with
	       the proper screw connections immediately.

	    4) There should be no signs of overheating: darkened connections,
	       melted insulation, or "baked" fixtures.  Any such damage should
	       be repaired.
	    
	    5) Connections between aluminum and copper wire need to be
	       handled specially.  Current Canadian codes require that the
	       wire nut used must be specially marked for connecting
	       aluminum to copper.  The NEC requires that the wire be
	       connected together using special crimp devices, with an
	       anti-oxidant grease.  The tools and materials for the latter
	       are quite expensive - not practical to do it yourself unless
	       you can rent the tool.

	    6) Any non-rated receptacle can be connected to aluminum wiring
	       by means of a short copper "pigtail".  See (5) above.
	    
	    7) Shows reasonable workmanship: neat wiring, properly stripped
	       (not nicked) wire etc.
    
	If, when considering purchasing a home, an inspection of the wiring
	shows no problems or only one or two, we believe that you can consider
	the wiring safe.  If there are signs of problems in many places,
	we suggest you look elsewhere.  If the wrong receptacles are used,
	you can replace them with the proper type, or use pigtails - having
	this professionally done can range from $3 to $10 per receptacle/
	switch.  You can do this yourself too.

------------------------------
Subject: I'm buying a house!  What should I do?

	Congratulations.  But...  It's generally a good idea to hire
	an inspector to look through the house for hidden gotchas.
	Not just for wiring, but plumbing and structural as well.  If an
	inspection of the wiring shows no problems or only one or two minor
	ones, we believe that you can consider the wiring safe (after any
	minor problems are fixed).  If there are signs of problems in many
	places, we suggest you look elsewhere.

	Here's some hints on what to look for:

	Obvious non-code wiring can include:

		- Zip cord wiring, either concealed or nailed to walls
		- Hot wiring on the identified (neutral) conductor without
		  proper marking.
		- Ungrounded grounding outlets (except when downstream of
		  a GFCI)
		- Splices hanging in mid-air (other than proper knob-and-tube)
		- Switched neutrals
		- Unsecured Romex swinging about like grapevines

	Certain wiring practices that are actually to code (or were at one
	time) sometimes reveal DIY wiring that may have hidden violations:

		- Switches that seem to control nothing (abandoned, perhaps
		   not properly terminated wiring)
		- A wall switch that controls things that you think it
		  shouldn't, for instance mysteriously removing power
		  from lights or outlets in other rooms. 
		- Switches and outlets in bizarre locations
		- Great numbers of junction boxes without outlets or lamps
		- Junction boxes with great numbers of wires going into them
		- Wiring that passes through a closet instead of a wall or
		  ceiling
		- Backwrapped grounding wires (ground wire wrapped around
		  the incoming cable insulation outside the box).
		- A breaker or fuse for outside wiring that is near the bottom
		  of the breaker panel or in an add-on fusebox.  The outdoor
		  wiring may have been homeowner-installed after the house was
		  built, and was not buried deep enough or was done with the
		  wrong kind of wire.   

------------------------------
Subject: What is this weird stuff?  Old style wiring
	
	In the years since Edison "invented" electricity, several different
	wiring "styles" have come and gone.  When you buy an older home you
	may encounter some of this stuff.  This section describes the old 
	methods, and some of their idiosyncrasies.

	The oldest wiring system you're likely to encounter is called
	"knob and tube" (K&T).  It is made up of individual conductors with
	a cloth insulation.  The wires are run along side structural
	members (eg: joists or studs) using ceramic stand-offs (knobs).
	Wire is run through structural members using ceramic tubes.  Connections
	were made by twisting the wire together, soldering, and wrapping
	with tape.  Since the hot and neutral were run separately,
	the wiring tends to be rather confusing.  A neutral often runs
	down the centre of each room, with "taps" off to each fixture.
	The hot wire tended to run from one fixture to the next.  In some
	cases K&T isn't colour-coded, so the neutral is often the same
	colour as the hot wires.

	You'll see K&T in homes built as late as the 40's.

	Comments on K&T:

		- the people installing K&T were pretty paranoid about
		  electricity, so the workmanship tends to be pretty good.
		- The wire, insulation and insulators tend to stand up
		  very well.  Most K&T I've seen, for example, is in
		  quite good condition.
		- No grounding.  Grounding is usually difficult to install.
		- boxes are small.  Receptacle replacement (particularly with
		  GFCI) can be difficult.  No bushing on boxes either,
		  so wiring changes need special attention to box entry.
		- Sometimes the neutral isn't balanced very well between
		  separately hot circuits, so it is sometimes possible to
		  overload the neutral without exceeding the fusing on
		  any circuit.
		- In DC days it was common to fuse both sides, and no
		  harm was done.  In fact, it was probably a Good Thing.
		  The practise apparently carried over to K&T where
		  you may find fused neutrals.  This is a very bad
		  thing.
		- Building code does not usually permit insulation in
		  walls or ceilings that contains K&T.  Some jurisdictions
		  will allow it under some circumstances (eg: engineer's
		  certificate).
		- Connection to existing K&T from new circuits can be
		  tricky.  Consult your inspector.
		- Modern wiring practice requires considerably more
		  outlets to be installed than K&T systems did.
	
	Since K&T tends to be in pretty decent condition it generally
	isn't necessary to replace it simply because it's K&T.  What
	you should watch out for is renovations that have interfered
	with it and be cautious about circuit loading.  In many cases
	it's perfectly reasonable to leave existing K&T alone, and add
	new fixtures on new circuits using modern techniques.

	After K&T, they invented multi-conductor cable.  The first type
	you will see is roughly a cloth and varnish insulation.  It
	looks much like the romex cable of the last decade or two.
	This stuff was used in the 40's and 50's.  Again, no grounding
	conductor.  It was installed much like modern wiring.  Its
	major drawback is that this type of insulation embrittles.
	We've seen whole systems where the insulation would fracture
	and fall off at a touch.  BX cable of the same vintage has
	similar problems.  It is possible for the hot conductor to
	short out to the cable jacket.  Since the jacket is rusted, it
	no longer presents a low resistance return path for the current
	flow, but rather more acts like a resistance heater.  In
	extreme cases the cable jacket will become red hot without
	blowing the fuse or circuit breaker.  The best thing to do with
	old style BX is to replace it with modern cable whenever it's
	encountered and there's any hint of the sheath rusting.

	This stuff is very fragile, and becomes rather hazardous if the
	wires become bare.  This wiring should be left untouched as
	much as possible - whenever an opportunity arises, replace it.
	A simple receptacle or switch replacement can turn into a
	several hour long frustrating fight with electrical tape or
	heat-shrink tubing.

	After this wiring technique, the more modern romex was
	invented.  It's almost a asphalt impregnated cloth.  Often a
	bit sticky.  This stuff stands up reasonably well and doesn't
	present a hazard and is reasonably easy to work with.  It does
	not need to be replaced - it should be considered as safe as
	the "modern" stuff - thermoplastic insulation wire.  Just don't
	abuse it too much.

------------------------------
Subject: Where do I buy stuff?

	Try to find a proper electrical supply outlet near you.  Their
	prices will often be considerably better than chain hardware stores or
	DIY centres, have better quality materials, have wider variety
	including the "odd" stuff, and have people behind the counter that
	know what you're talking about.  Cultivate friendly knowledgeable
	sales people.  They'll give you much valuable information.

------------------------------
Subject: Copper wire characteristics table

	These are taken from the Amateur Radio Relay Handbook, 1985.

	AWG  dia    circ  open   cable  ft/lb   ohms/
	     mils   mils  air A  Amp    bare    1000'

	10   101.9 10380    55    33    31.82   1.018
	12    80.8  6530    41    23    50.59   1.619
	14    64.1  4107    32    17    80.44   2.575

	We don't show specs for 8ga or larger because they're
	usually stranded.

	Mils are .001".  "open air A" is a continuous rating for
	a single conductor with insulation in open air.  "cable amp"
	is for in multiple conductor cables.  Disregard the amperage
	ratings for household use.

	To calculate voltage drop, plug in the values:
		
		V = DIR/1000'
	
	Where I is the amperage, R is from the ohms/1000' column
	above, and D is the total distance the current travels (don't
	forget to add the length of the neutral and hot together - ie:
	usually double cable length).  Design rules in the CEC call
	for a maximum voltage drop of 6% (7V on 120V circuit)

------------------------------
Subject: Smoke detector guidelines

	Many (most?) building codes now require the installation of
	smoke detectors in homes.  In fact, this has been made
	retroactive in many municipalities.

	There are many different types of smoke detectors.  Ionization,
	photo-cell, battery-powered, AC-powered etc.  The only thing
	we're concerned with here, is AC versus battery powered, other
	than to comment that most building codes are based around
	ionization detectors, photocell units being usually for
	somewhat more specialized purposes.  All things being equal, in
	a residential setting with the "ordinary fire", an ionization
	detector will detect smoke before a photo-cell will - indeed,
	in some fires, the smoke is almost invisible, and less likely
	to trip a photo-cell.

	There is another type of fire detectors - "heat detectors".
	These work usually by a small piece of special metal melting at
	110F or so.  These are much better at avoiding false trips.
	But they usually take much longer to trip than a smoke detector, and
	should usually only be considered for triggering sprinkler
	devices (where the consequences of a false trip are quite
	severe).  Heat detectors should not be used as primary fire
	detection.

	Most building codes that mandate detectors mandated AC-powered
	ones for new construction.  This is because the statistics show
	that, in houses equipped with smoke detectors, a lot more
	people were getting killed in houses with battery-only
	detectors that had dead batteries than were getting killed in
	houses where the breakers tripped and killed an AC-only
	detector.  It's also worth noting that some battery detectors
	are quite sensitive about battery condition.  Some even refuse
	to work if the battery is zinc-carbon (standard cheap battery)
	instead of alkaline (more expensive).

	Our building code discourages the installation of smoke
	detectors on circuits used for other purposes.  This means that
	only a main-panel breaker trip can kill the detectors.  A
	main-panel trip is unlikely even in a fire started by an
	electrical fault until well after the fire has really engulfed the
       home.

	These codes also usually require that the AC detectors be
	interconnected so that if one triggers, they all sound the
	alarm.  This is usually done by an additional wire between the
	units.

	The above suggests that the best way of doing things is to have
	one circuit dedicated for smoke detectors, and you run 14-3
	between each of the detectors - the red wire being the "gang
	trip" control.

	If you're still concerned about losing power and thereby losing
	your detectors, we suggest either the use of detectors that run
	off AC power with battery backup, OR, adding battery detectors
	into a system that's already adequately covered with AC detectors.

	Battery-only detectors should only be considered a stopgap
	measure in putting detectors into a house that doesn't have any
	detectors at all, or adding redundancy into a system that already
	has AC detectors.

	We also suggest that, if you have battery detectors, you make
	changing the battery a yearly (or semi-yearly) scheduled event.
	Some people change the batteries on their birthdays.  Others
	change the batteries during a "daylight/standard time change"
	maintenance pass.

	We don't recommend waiting for the detector to tell you that the
	battery is dead, unless you manually test the detector monthly.
-- 
Chris Lewis: _Una confibula non sat est_
Latest psroff: ftp://ftp.uunet.ca/distrib/chris_lewis/psroff3.0pl17/*
Latest hp2pbm: ftp://ftp.uunet.ca/distrib/chris_lewis/hp2pbm/*
NNTP AUTHINFO GENERIC info: ftp://ftp.uunet.ca/distrib/chris_lewis/generic/*
Wiring FAQ Part 1

Shop Talk Home Page